Crestron Green Light DIN-HUB Guía de instalación Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 32
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
DIN Rail Analog Output Module Crestron DIN-AO8
Connectors, Controls & Indicators (Continued)
# CONNECTORS*,
CONTROLS &
INDICATORS
DESCRIPTION
5 OVERRIDE with LEDs
and Button
(2) 2-pin 3.5 mm detachable
terminal blocks, paralleled
Max Wire Size: 1.5 mm
2
(16 AWG)
Sensing input for external
low-voltage contact closure
Triggers module’s override
state when a closure is present
Minimum Override Switch
Rating:
10 mA (per module) at 24 Volts
(1) Red LED and (1) miniature
pushbutton for enabling manual
override and saving override
preset levels. For more
information, refer to “Operation”
on page 21.
6 PWR (1) Green LED, illuminates
when DC power is applied to
the NET port
7 NET (1) Yellow LED, indicates
communication with the control
processor
8 RESET (1) Recessed miniature
pushbutton, resets internal
processor
* Interface connectors for NET, OVERRIDE and OUTPUT ports are provided
with the unit.
8 DIN Rail Analog Output Module: DIN-AO8 Operations & Installation Guide – DOC. 6663A
Vista de pagina 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 31 32