Crestron CHV-RTS & CHV-RTHS Temperature & Humidity Sensors
Installation Guide DOC. 8189D Temperature/Humidity Sensors: CHV-RTS/CHV-RTHS 9
Problem Solving
Troubleshooting
The following table provides corrective action for possible trouble
situations. If further assistance is required, please contact a Crestron
customer service representative.
CHV-RTS and CHV-RTHS Troubleshooting
TROUBLE POSSIBLE
CAUSE(S)
CORRECTIVE ACTION
The thermostat
is not receiving
a signal.
Improper
connection
between the
sensor and the
thermostat.
Check the connection
between the sensor and
thermostat (refer to
Hardware Hookup,” on
page 5).
Incomplete
(open) circuit
exists in wiring.
Check the connection
between the sensor and
thermostat (refer to
Hardware Hookup,” on
page 5).