CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 26 09 43 - 7
2.2 SYSTEM CHARACTERISTICS
A. Web-accessible, network-connected programmable lighting control system that receives digital
or analog signals from addressable input devices, assembles signals at central signal processor,
and distributes operating signals to addressable control devices that effect a change in state.
1. Electronic power switching modules and relays process signals and effect circuit on-off
switching, emergency switching, and 0 10V fluorescent dimming where indicated.
Emergency switching overrides preset state and puts each circuit to the programmed
emergency condition. Buttons on the module provide manual disconnect and manual
circuit testing.
2.3 NETWORK LIGHTING CONTROL PANELS
Specifier: Crestron Green Light Network lighting control panels are expandable from 8 to 56 circuits and
are available with lug only mains and branch circuit protection, main disconnect and branch circuit
protection, or feed-through type requiring separate branch circuit protection.
A. Control Panels, General: Comply with NEMA PB 1 and UL 50 (CAN/CSA C22.2, No. 94), UL 67
(CSA C22.2, No. 29), UL 489 (CAN/CSA C22.2, No. 65), and UL 916 (CSA C22.2, No. 205).
Specifier: Retain panel types required for project.
B. Circuit Protected Network Lighting Control Panels: Arc-less high inrush.
1. Basis of Design Product: Crestron, Green Light Power Switching Network
Lighting Control panel Model GLPS-HSW.
2. Main Circuit: [Main circuit breaker as indicated] [Main Lugs Only] [60 amp main circuit
breaker] [80 amp main circuit breaker] [100 amp main circuit breaker] [125 amp main
circuit breaker].
3. Branch Circuit Protection: [120/208] [277/480] 20 amp thermal magnetic type.
4. Switching Relay Types: Arc-less high inrush, lifetime rated minimum 1,000,000 on/off
cycles, with air gap off protection.
5. Cabinet Capacity: [12 circuits] [30 circuits] [42 circuits] [As required for circuits
indicated.
C. Line Protected Network Lighting Control Panels: Standard high inrush.
1. Basis of Design Product: Crestron, Green Light Power Switching Network
Lighting Control panel Model No. GLPS-SW.
2. Main Circuit: [Main circuit breaker as indicated] [Main Lugs Only] [60 amp main circuit
breaker] [80 amp main circuit breaker] [100 amp main circuit breaker] [125 amp main
circuit breaker].
3. Branch Circuit Protection: [120/208] [277/480] 20 amp thermal magnetic type.
4. Switching Relay Types: Standard high inrush, lifetime rated minimum 10,000 on/off
cycles, with air gap off protection.
5. Cabinet Capacity: [12 circuits] [30 circuits] [42 circuits] [As required for circuits
indicated.
D. Feed-Through Network Lighting Control Panels: Arc-less high inrush.
1. Basis of Design Product: Crestron Green Light Express Power Switching Network
Lighting Control panel Model No. GLPS-HSW-FT.