Crestron CEN-COM Guía de instalación Pagina 29

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 40
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 28
Crestron CEN-HPRFGW High Powered RF Gateway
Problem Solving
Troubleshooting
The following table provides corrective action for possible trouble
situations. If further assistance is required, please contact a Crestron
customer service representative.
CEN-HPRFGW Troubleshooting
TROUBLE POSSIBLE
CAUSE(S)
CORRECTIVE
ACTION
Incorrect power
supply.
Use a Crestron power
supply with sufficient
power for the network.
PWR LED does
not illuminate.
CEN-HPRFGW is
not receiving
sufficient power.
Use the Crestron
Power Calculator to
help calculate how
much power is
needed for the
system.
NET LED does
not illuminate.
CEN-HPRFGW
Net ID is not set to
match the Net ID
of the SIMPL
program.
In Crestron Toolbox,
check Functions |
CresnetID to verify
Net ID. Verify SIMPL
Windows program ID.
CEN-HPRFGW is
not communicating
with network.
Check network cabling
for solid connections
and correct pinouts.
NET LED is on
but unit does
not
communicate
with touchpanel.
CEN-HPRFGW
Net ID is not
unique; two or
more units share
the same Net ID.
Verify the Net IDs for
all CEN-HPRFGWs
are unique when
multiple units are
used.
(Continued on following page)
Operations & Installation Guide – DOC. 6587B High Powered Gateway: CEN-HPRFGW 25
Vista de pagina 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 39 40

Comentarios a estos manuales

Sin comentarios