6.4" Lectern/Wall Mounted Touchpanel Crestron Isys™ TPS-3000L
NOTE: All network wiring must consist of two twisted pairs. One twisted pair is
the +24V conductor and the GND conductor. The other twisted pair is the Y and Z
conductors.
NOTE: When daisy-chaining Cresnet units, strip the ends of the wires carefully to
avoid nicking the conductors. Twist together the ends of the wires that share a pin on
the network connector, and tin the twisted connection. Apply solder only to the ends
of the twisted wires. Avoid tinning too far up the wires or the end becomes brittle.
Insert the tinned connection into the Cresnet connector and tighten the retaining
screw. Repeat the procedure for the other three conductors.
NOTE: For larger networks (i.e., greater than 28 network devices), it may become
necessary to add a Cresnet Hub/Repeater (CNXHUB) to maintain signal quality
throughout the network. Also, for networks with lengthy cable runs, it may be
necessary to add a Hub/Repeater after only 20 devices.
Identity Code
Every equipment and user interface within the network requires a unique Cresnet
identity code (NET ID). These codes are recognized by a two-digit hexadecimal
number ranging from 03 to FE. Refer to “Interface Menu” on page 13 for
instructions on setting the unit's NET ID. The NET ID of the unit must match the
NET ID specified in the SIMPL Windows program. Refer to “Setting the Net ID in
Device Settings” on page 26 for information about changing the ID in a SIMPL
Windows program.
Screen Orientation
When installing the TPS-3000L into a wall or lectern, the screen must be properly
oriented for optimum viewing. Incorrect orientation of the screen will not allow the
screen to be viewed at its brightest during operation.
Wall Mounting
The TPS-3000L ships in the default “Upright” configuration for mounting in a wall.
The “Upright” configuration provides optimum viewing when installed into a wall.
In this setting, the pushbuttons are located on the left side of the screen, and the
screen orientation is set to “Upright” (refer to the “Orientation” section of “Screen
Settings” which begins on page 15 for instructions) with the connectors located on
the bottom of the touchpanel. Refer to the following diagram.
Pushbutton Layout and Join Number Assignment Wall Mount
1
2
3
4
5
8 • 6.4 Inch Lectern/Wall Mount Touchpanel: Crestron Isys™ TPS-3000L Operations Guide – DOC. 6077