Application of EN 15232 gives rise to diffe-
rent energy effi ciency factors for different
building types, with regard to the use of ther-
mal and electrical energy. In the evaluation
of buildings, the energy effi ciency class C is
the reference class for the implementation
of measures for energy optimisation.
The red fi eld in the table on the right-hand
side shows how the thermal energy con-
sumption of a building with effi ciency class
A with a factor of 0.7 can be reduced by up
to 30 %.
VDI 3813 – room automation
VDI 3813 describes the integrated room auto-
mation with special consideration for intero-
perability of different building systems, based
on usage requirements. To provide a uniform
assessment basis for owners, planners and
system integrators, clear terms and functions
are defi ned in the norm.
The current diffi culty is that in invitations
to tender, room automation functions are
dealt with separately from the building sys-
tems connected with technical development.
In practice, this often means that existing
potential for saving energy remains unused.
The VDI 3813 supplements the EN 15232
by providing a precise description of the
room automation functions described there.
It is important that EN 15232 and VDI 3813
are applied as early as the basic evaluation
and pre-planning stage.
The table on the right-hand side shows the
room automation functions of the VDI 3813,
relating to the energy effi ciency classes of
EN 15232.
Basic principles and standards of building automation | Use in room automation
Building Automation and Control (BAC)
Effi ciency classes EN 15232
Effi ciency factor
for thermal
energy
Effi ciency factor
for electrical
energy
Offi ce
School
Hotel
Offi ce
School
Hotel
A
Highly effi cient Building Automation and Control System
(BACS) and Technical Building Management (TBM)
0.70 0.80 0.68 0.87 0.86 0.90
B Advanced BACS and TBM 0.80 0.88 0.85 0.93 0.93 0.95
C Standard BACS 1.00 1.00 1.00 1.00 1.00 1.00
D Non-effi cient BACS 1.51 1.20 1.31 1.10 1.07 1.07
Application function
BAC effi ciency
classes in ac-
cordance with
DIN EN 15232
DCB
A
Basic functions affecting energy effi ciency
Occupancy control x x
Time program
x
x
Illumination functions which infl uence energy effi ciency
Light switching x
Automatic lighting
x
x
Daylight switching
x
x
Constant light control
x
x
Solar shading functions which infl uence energy effi ciency
Automatic solar shading x
Louvre adjustment
x
x
Shading correction
x
x
Thermo-automatic control
x
x
Air conditioning functions
Energy level selection x
x
Energy level selection with start optimisation
x
x
Target value calculation
x
x
Function selection
x
x
Temperature control (heating/cooling)
xx
x
Room/intake air temperature cascade control
x
x
Ventilator control
x
x
Sequence control
x
x
Setpoint control
x
x
Air quality control/regulation
x
Night cooling
x
x
Load optimisation
x
x
Source: VDI 3813 part 2
Source: DIN EN 15232, table 9, table 11