Thermostats Crestron CHV-TSTAT and CHV-THSTAT
24
Thermostats: CHV-TSTAT and CHV-THSTAT Operations and Installation Guide – DOC. 8163E
Thermostat Setup
Setup Procedure
After the thermostat is installed, it is necessary to set it up for a particular
heating/cooling system. There are nine types of heating and cooling systems. The
available choices displayed on the setup screens depend on the type of system
selected. Follow these directions to access the setup screens.
1. Press and hold the MODE and VIEW buttons simultaneously for 5 seconds
to access the setup menus.
2. Press VIEW to select the parameter. A box appears around the selected
parameter.
3. Press the arrow keys (▲▼) to choose the value of the selected parameter.
4. Use the MODE button to advance to the next setup screen.
CHV-TSTAT and CHV-THSTAT Setup
MODE
VIEW
CRESTRON
Advance to next
selection on current
Setup Screen
Change value
of selected
parameter
Advance to next
Setup Screen
Setup Notes
The following are general setup notes.
NOTE: Refer to “System Connections” on page 10
for remote sensor connections to
the thermostat.
NOTE: The Offset option permits recalibration of the room temperature sensor. The
offset is the number of degrees added to or subtracted from the actual temperature.
The range is -6° to +6° F. Factory default is 0° F. This adjustment changes the actual
regulated temperature, not just the display.
NOTE: The sensors are used for temperature and humidity averaging. Choose USE
to include each sensor, or OMIT to exclude each sensor in the averaging equation.
Sensors that have the same designation (for example, outdoor) are averaged together.
NOTE: The thermostat does not leave Setup mode unless a valid sensor selection is
made.