Control System Error Log Message Formats
When a remote sensor that has been designated as USE, SLAB, or OD in the Setup
Sensors screen (refer to “Thermostat Setup”, which begins on page 24) generates an
error, a message is sent to the error log. Retrieve this message using the System Info
tool in Crestron Toolbox:
1. Using Crestron Toolbox, select Tools|System Info.
2. Select the control system from the address bar and examine the Error Log.
Error Message Format
Sensor <channel> type <designator> <CHA errors>, <CHB
errors> Errors @ <cycle count>
Where:
channel is the sensor channel string
designator is the sensor setup designation
CHA errors/CHB errors are the number of errors on each sub-channel
cycle count is the number of read cycles that have occurred.
NOTE: Both sub-channels have their error count reported, regardless of the sensors
connected.
This message is sent upon the first error detected on the channel, as well as every
100 errors detected thereafter. When only one sensor is connected to a remote
interface, its values assume the <CHA> position. The values for the <CHB> position
are not used. When two sensors are connected to a remote interface, the <CHA>
position indicates the errors for the first sensor, and the <CHB> position indicates
the errors for the second sensor.
The following is an example output, as seen in Crestron Toolbox, when a single
outdoor sensor connected to RS1 accumulates 101 read failures:
Error: Message from device Slot-09.ID-2A: Sensor R1T
type OD: 101,3922 Errors @ 3922 (0056:0000:0056)
The following is an example output, as seen in Crestron Toolbox, when two air space
sensors are connected to RS1 and the first sensor encountered a read failure:
Error: Message from device Slot-09.ID-2A: Sensor R1T
type USE: 1,0 Errors
@ 5943 (0056:0000:0056)