Crestron CHV-TSTATEX Guía de instalación Pagina 53

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 92
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 52
Crestron CHV-TSTAT and CHV-THSTAT Thermostats
Operations and Installation Guide DOC. 8163E Thermostats: CHV-TSTAT and CHV-THSTAT
47
Slab 4A – 2-Stage Heat/1-Stage Cool with Slab Maximum
Press and hold the MODE and VIEW buttons simultaneously for 5 seconds to enter setup mode.
SETUP: SYSTEM
SETUP: SYSTEM
Heat Sys Type:
Slab MAX T:
SLAB 4A
122
o
2 STG SPACE HEAT - 1 STG
COOL WITH SLAB MAX (H/C)
SLAB = (W1), HT = W2, CL = Y1
Press To Continue
Heat System Type: SLAB 4A
Slab MAX T: Select 39°122° F (39° 50° C). Used to
prevent the floor from becoming too hot on long heat calls.
NOTE: Slab mode 4A requires an air temperature source
and a slab remote sensor (CHV-RSS, sold separately).
SETUP: SYSTEM PERFORMANCE
SETUP: SYSTEM PERF
Heat Anticipator:
Cool Anticipator:
Intrstg Differential:
5
2
2.0
0
ADJUSTS HEAT SHUTOFF DYNAMICS
Press To Continue
Heat and Cool Anticipator: Select 16.
Low number = more frequent cycles, faster response. High
number = less frequent cycles, slower response.
Interstage Differential: Select 0.5º8.0º F.
The proportional temperature error to trigger the second stage.
SETUP: HUMIDITY OPTIONS
SETUP: HUM OPTS
Show Hum Mode Pg:
Show Hum View Pg:
Cold Weather Comp:
Y
Y
N
SYSTEM ENABLE/DISABLE
PAGE
SETUP: HUM OPTS
Invert Hum Output Y
Call FAN in HUM: N
INVERTED HUM RELAY LOGIC
HUM ABOVE SP = ENERGIZED
Press To Continue
Show Hum Mode Pg and Show Hum View Pg: Select Y to show
humidity page in normal operation.
Cold Weather Compensation: Modifies the humidifier output
to prevent condensation on the windows. Requires an outdoor
temperature source (CHV-THSAT or CHV-TSTAT with
CHV-RTHS CHV-RTS, or CHV-RSS, sensors sold
separately).
Invert Hum Output: Reverses the logic controlling the
switching of the HUM relay (NO/NC). May be useful when
using to control a dehumidifier.
NOTE: Most dehumidifier applications require the default
setting.
Call FAN in HUM: Makes a fan call during humidity calls
instead of waiting for a heating or cooling call to trigger fan.
NOTE: Most dehumidifier applications automatically trigger
fan operation.
NOTE: This setting is only useful for humidity calls with
normal (non-inverted) logic.