Crestron CHV-TSTAT and CHV-THSTAT Thermostats
Operations and Installation Guide – DOC. 8163E Thermostats: CHV-TSTAT and CHV-THSTAT
29
SETUP: DISPLAY OPTIONS
SETUP: DISP OPTIONS
Temperature Units:
Temp Disp Offset:
Dual Setpoint Auto:
Main Scn Lwr Obj:
Use 0.5 Deg C Step:
F
0
0
Y
HM
Y
Temperature Units: Display temperature units in (F)
Fahrenheit or (C) Celsius.
Temp Disp Offset: Select -6° – +6° F. Allows the user to
adjust the displayed and regulated temperature.
Dual Setpoint Auto: Enables 2-point auto mode.
Main Scn Lwr Object:
SB – Slab OD – Outdoor
HM – Humidity NA – None
Use 0.5 Deg C Step: Display in 0.5° C steps.
SETUP: OTHER SETTINGS
SETUP:
OTHER SETTINGS
Wide Range Cool:
Run Fan in Ht Calls:
Auto DdBand Deg:
Disable Auto Mode:
N
N
2
0
N
EXTENDED COOL SETPOINT
RANGE 38-99F (3-37C)
Wide Range Cool: Extends cool setpoint to full auto range of
38º – 99º F (3º – 37º C).
Run Fan in Ht Calls:
Options available if # heat stages = 1:
Y: Select if the heating system requires fan control.
N: Disables fan call operation for heat calls.
Options available if # of heat stages = 2:
--: Disables fan call operation for heat calls.
1/2: Fan called for first and second stage.
2: Fan called for second stage only.
NOTE: Most heating systems run the fan automatically.
Auto DdBand Deg: (2 – 6) The minimum differential
between heating and cooling setpoints (Dual Setpoint Auto
set to Y in “Display Options”).
Disable Auto Mode: Does not display Auto on “System
Mode” screen and does not permit entering Auto mode even
SETUP: SENSORS
SETUP: SENSORS
SENSOR
INTERNAL:
REMOTE 1:
REMOTE 2:
>TEMP HUM
USE OMIT
SLAB
DETECTED: 1 x T
INTERNAL: Choose USE or OMIT. Choose USE to permit
temperature averaging.
NOTE: Sensor temperature and humidity can be output to
network even if OMIT is chosen.
REMOTE 1 and 2: Choose USE, OMIT, OD (outdoors), or
SLAB (remote sensors only).