230 V Lighting Design Guide
Doc. 4859C | crestron.com
23
Double Width Enclosure Mounting
The module and associated terminal block are installed in a double width enclosure. The PAC2 processor occupies
the lowest module position.
Module Bypass Jumpers
CAUTION: A bypass jumper is provided to allow testing and to protect the module during installation. When properly
secured by nine screws, the jumper on the black and red section of the terminal block shorts the line to the output
so that the circuit is energized. Do not remove the bypass jumper until all feed and load wiring has been completed,
the circuit has been tested for electrical faults, and the module has been installed. The jumper on the white section
of the terminal block ties the neutral in to the neutral outs. This jumper should never be removed.
NOTE: Use copper conductors only—rated 75° C.
Cresnet Terminal Block for CAEN Automation Enclosures
The CAEN-BLOCK is a Cresnet terminal block designed specifically for Crestron lighting and automation systems to
link extension enclosures and satellite enclosures to the central PAC2 or PAC2M control system. The CAEN-BLOCK
mounts at the bottom of each CAEN enclosure that does not contain a control system to provide Cresnet and
Override signal connectivity for CLXI-Series lighting control modules within. The CAEN-BLOCK serves as a parallel
distribution block for multiple Cresnet cables, and provides for connection of the Cresnet and override signal cables
from the central control system.