Crestron CHV-TSTATEX-FCU infiNET EX Thermostat (Fan Coil Unit)
Operations & Installation Guide DOC. 7206C infiNET EX Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU
9
Setup
Identity Code
NOTE: The latest software can be downloaded from the Crestron Web site
(www.crestron.com/software).
Every CHV-TSTATEX-FCU communicating via RF with a Crestron control system
through a CEN-RFGW-EX wireless gateway or directly with an MC3 3-Series
Control System requires a unique RF ID. The RF ID is a two-digit hexadecimal
number that can range from 03 to FF. The RF ID of the unit, set using Crestron
Toolbox™, must match the RF ID specified in the Crestron Studio or SIMPL
Windows program.
Supplied Hardware
The hardware supplied with the CHV-TSTATEX-FCU is listed in the following
table.
Supplied Hardware for the CHV-TSTATEX-FCU
DESCRIPTION PART
NUMBER
QUANTITY
Screws, Zinc, Phillips, Pan Head, #06-32 x 1” 2007251 2
Batteries, AA, Alkaline 2001050 2
Installation
NOTE: Installers should have a strong working knowledge of HVAC systems.
The location of the thermostat can affect its performance and efficiency. Install the
thermostat away from direct sunlight, drafts, doorways, skylights and windows. Also
make sure the thermostat is conveniently located for control access and setup.
Thermostats should be mounted 60 inches (~1.6 meters) above the finished floor
(HVAC industry standard). Do not mount on an exterior wall.
The following tools and hardware are required for installation:
Standard 1-gang electrical box, mounted horizontally (not supplied)
Phillips screwdriver (not supplied)
Two 1-inch pan head Phillips screws (included)
Two AA batteries (included)
Use the following procedure to install the CHV-TSTATEX-FCU in a standard,
1-gang electrical box (refer to illustration on the following page):
1. Turn HVAC system power OFF.
2. Separate thermostat front plate from rear plate. It may be necessary to exert
force when removing the front plate.