Crestron CHV-TSTATEX-FCU Guía de instalación Pagina 21

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 40
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 20
Crestron CHV-TSTATEX-FCU infiNET EX Thermostat (Fan Coil Unit)
Operations & Installation Guide DOC. 7206C infiNET EX Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU
17
2. Ensure the unit is in Setup mode (refer to “Basic Setup - Basic Thermostat
Setupabove or “Setup Mode” which starts on page 18) and that Acquire
mode (AC) is selected.
3. Press MODE until the infiNET EX IDfunction is displayed (id).
Use
and to choose the infiNET EX ID.
4. Press MODE until the Start infiNET EX Acquirefunction is displayed
(AC).
5. Press
or on the CHV-TSTATEX-FCU to start the acquire process: The
display shows flashing (in progress). When finished, the display shows
00 (finished, found gateway) orE#(finished, could not find gateway),
where # represents an error code.
6. Once all devices have been acquired, take the CEN-RFGW-EX out of
Acquire mode by pressing its ACQUIRE button. Press FAN on the
thermostat to exit Setup mode.
NOTE: The acquire process can take up to 15 seconds. The acquire process cannot
be aborted.
NOTE: E1 indicates that search time has expired and no gateway was found. To
enable the channel, refer to “Start infiNET EX Acquire” in “Setup Mode
Parameters/Functions” which starts on page 19
.
Leaving an infiNET EX Network
To leave a network, press and hold the FAN, and buttons simultaneously for 5
seconds. Press MODE until the unacquire function is displayed (UA). Press
or on the CHV-TSTATEX-FCU to start the unacquire process. Refer to
Verifying Communication Status” on page 21 for a list of codes displayed once the
process is completed. Press FAN on the thermostat to exit Setup mode.
Vista de pagina 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 39 40

Comentarios a estos manuales

Sin comentarios