infiNET EX Thermostat (Fan Coil Unit) Crestron CHV-TSTATEX-FCU
22
infiNET EX Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU Operations & Installation Guide DOC. 7206C
Self-Test Results
These error/status codes are returned when performing a self-test operation, enter
Setup mode as described in “Basic Thermostat Setup” which starts on page 16. Press
MODE until the AC, UA or CC function is displayed. Press
or on the
CHV-TSTATEX-FCU to verify the communication status.
Self-Test Error Codes
ERROR
CODE
SUMMARY CORRECTIVE ACTION REMARKS
00 Success None No detectable problems found.
E0 Low battery
warning
Check and/or replace
batteries
Error is only returned when current power
configuration requires batteries
E1 24 Vac usage
warning
Check power configuration Error is set when 24 Vac appears to be
available but is not configured properly (slide
switch position)
E2 Display
operation
Return unit Device display may not be operating properly
E3 NV memory
usage
Replace unit if feasible Retention of non-volatile setup and operation
parameters may be compromised
E4 Poor link quality Perform general network
debugging
Poor communication link to gateway may be
consuming extra power and lowering battery life
E5 Gateway
acquire
information
Acquire device or check
network
Device cannot communicate with a gateway.
Normal result for unacquried device
E6 Network
communication
error
Additional network
communication issues
detected
Normal result for unacquired device
E7 Poor network
communication
Additional indicator of poor
communications link
Often associated with excessive network hops;
Consider moving device closer to gateway or
splitting network with additional gateways for
better coverage