infiNET EX Thermostat (Fan Coil Unit) Crestron CHV-TSTATEX-FCU
24
infiNET EX Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU Operations & Installation Guide DOC. 7206C
Dual Setpoint Auto Mode (“AU” = “d” in Setup Mode)
In dual setpoint Auto mode, separate heat and cool setpoints are used. When the
ambient temperature drops below the heat setpoint, the unit calls for heat to maintain
the heat setpoint. When the ambient temperature rises above the heat setpoint, the
unit does not call for cooling until the temperature exceeds the cool setpoint. When
the ambient temperature drops below the cool setpoint, the unit does not call for
heating until the temperature is below the heat setpoint.
When dual setpoint Auto mode has been enabled, the Auto Dead Band is used to
maintain a minimum separation between the heat and cool setpoints. If this
separation is violated by a setpoint adjustment, the other setpoint is automatically
adjusted.
For example, if the heat setpoint is at 68 degrees, the cool setpoint is at 72 degrees
and the Auto Dead Band is set to 4 degrees, if the cool setpoint is lowered to 71
degrees, the heat setpoint is automatically adjusted to 67 degrees to maintain the 4
degree Auto Dead Band separation.
In dual setpoint Auto mode, the CHV-TSTATEX-FCU display indicates whichever
setpoint is closer to the ambient temperature. Both the heat and cool setpoints can be
viewed simultaneously using a touch screen.
NOTE: When using a Dual setpoint, the CHV-TSTATEX-FCU has a 20 minute
change limiter to prevent system toggling.
Single Setpoint Auto Mode (“AU” = “S” in Setup Mode)
In single setpoint Auto mode, a single setpoint is used for regulation at all times,
regardless of whether the system is heating or cooling. The Auto Dead Band (db)
setup parameter is used to determine when to switch between heating and cooling.
For example, if the setpoint is at 70 degrees and the Auto Dead Band is set to 2
degrees, if the system is cooling, it does not start heating until the ambient
temperature drops below 68 degrees (setpoint Auto Dead Band). Once the unit has
switched to heating, it does not resume cooling until the ambient temperature rises
above 72 degrees (setpoint + Auto Dead Band).
A larger value for the Auto Dead Band setting results in less cycling between heating
and cooling but can result in large temperature swings during the course of the day.
Smaller values for the Auto Dead Band setting results in tighter temperature
regulation but more frequent cycling between heating and cooling.
NOTE: When using a single setpoint, the CHV-TSTATEX-FCU has a 20 minute
change limiter to prevent system toggling.
Fan
The FAN button toggles the fan setting between fan AUTO, fan high (F3), fan
medium (F2) and fan low (F1). When set to AUTO, a fan call is made whenever the
system makes a cool call or when the system makes a heat call (if the DIP switch is
set to “Enabled”). When set to F3, F2 or F1 the fan always runs.
Setpoints
The setpoint is the user selectable temperature the system maintains.
The
and buttons change the current setpoint by one degree F or C.