infiNET EX Thermostat (Fan Coil Unit) Crestron CHV-TSTATEX-FCU
30
infiNET EX Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU Operations & Installation Guide – DOC. 7206C
Problem Solving
Troubleshooting
The following table provides corrective action for possible trouble situations. If
further assistance is required, please contact a Crestron customer service
representative.
CHV-TSTATEX-FCU Troubleshooting
TROUBLE POSSIBLE
CAUSE(S)
CORRECTIVE ACTION
No display. No power from
system.
Check for 24 Vac on 24C connector.
Check circuit breaker powering
furnace or boiler.
Check thermostat wiring.
Check batteries (if on battery power).
Incorrect mounting
to back plate.
Check thermostat mounting.
Device does
not follow
control system
commands.
Device is not
communicating
with the
CEN-RFGW-EX.
Open Crestron Toolbox and select the
Network Device Tree View. Expand
the tree until the gateway to be
managed is selected.
Right-click the NET ID of the selected
gateway to open the sub-menu and
select Functions | infiNET EX
Gateway… If device is not listed,
acquire the device to the infiNET EX
network (refer to ”Joining an infiNET
EX Network” which starts on page 16).
RF ID of device
(or the gateway
ID) is not set to
match the RF ID
of the Crestrib
Studio or SIMPL
Windows program.
Use the Network Device Tree infiNET
EX network in Crestron Toolbox to poll
the infiNET EX network. Verify that the
RF ID for the infiNET EX device is set
to match the RF ID specified in the
Crestron Studio or SIMPL Windows
program.
Heating/Cooling
system is not
operating.
No power to
thermostat.
Check circuit breaker.
Check for 24 Vac on 24C connector.
Check circuit breaker powering
furnace or boiler.
Recheck wiring connections.
Check batteries, replace if necessary.
Cannot change
setpoint setting.
The upper or lower
temperature limits
were reached.
Heat setpoint lower limit is 38º F
(3º C).
Cool setpoint high limit is 59º F
(37º C).
Heat setpoint high limit and cool
setpoint low limit is user defined and
is defined during setup in the “HL” and
“CL” screens.
Refer to “Setup Mode
Parameters/Functions” which starts
on page 19.
(Continued on following page)