infiNET EX Thermostat (Fan Coil Unit) Crestron CHV-TSTATEX-FCU
32
infiNET EX Thermostat (Fan Coil Unit): CHV-TSTATEX-FCU Operations & Installation Guide DOC. 7206C
CHV-TSTATEX Troubleshooting (Continued)
TROUBLE POSSIBLE
CAUSE(S)
CORRECTIVE ACTION
Wrong
temperature is
displayed.
Wrong
temperature scale.
Select F or C as necessary.
A Temperature
Offset has been
applied.
Reset Temperature Offset (refer to
Setup Mode Parameters/Functions
which starts on page 19).
Bad location. Ensure the thermostat is located away
from direct sunlight, drafts, doorways,
skylights and windows or exterior
walls.
Incorrect sensor
source.
Ensure that the settings on “ir” screen
recall the temperature from the correct
source. Refer to “Setup Mode
Parameters/Functions which starts
on page 19
for additional information.
Heat or cool
call occurs but
device does not
indicate a heat
or cool call.
Steal power
function may be
causing problems
with HVAC
system.
Change Power DIP Switch to 24VAC
and ensure that two AA batteries are
installed.
Improper wiring
connections.
Recheck wiring connections.